Parchment Water Tower Project

Agency: Kalamazoo
Level of Government: State & Local
Category:
  • C - Architect and Engineering Services - Construction
  • Y - Construction of Structures and Facilities
  • Z - Maintenance, Repair or Alteration of Real Property
Opps ID: NBD11717810825372808
Posted Date: Mar 5, 2024
Due Date: Mar 27, 2024
Solicitation No: Reference number: 90900-019.0
Source: https://www.kalamazoocity.org/...
Parchment Water Tower Project

Closing date March 27, 2024, 03:30 PM

  • Reference number 90900-019.0
  • Status Open
  • Summary It is the intent of these plans and specifications to provide for a contractor who shall provide all labor, materials, tools, and equipment necessary to perform exterior tank painting, interior tank spot repairs, and various other repairs on the Parchment Water Storage Tank.

NON- MANDATORY PRE-BID MEETING – Wednesday, March 13, at 10:00 a.m.

Parchment Water Tower, 350 Park Ave, Parchment, MI 49004

SCOPE OF WORK

Tank Information:

The structure is a 200,000-gallon spheroid tank with a low-water level of 76.25 ft. located at 350 Park Ave. in Parchment, Michigan.

The work includes:

Exterior: High pressure water clean (5,000 to 10,000 psi) and spot power tool clean to a

SSPC-SP11 standard. Apply a three (3) coat epoxy urethane fluoropolymer system.

Dry Interior: Spot power tool clean the spot failures throughout to a SSPC-SP11 standard. Apply a spot two (2) coat epoxy system to the prepared surfaces.

Foundation: Repair spalls. Water clean and apply a two (2) coat epoxy system.

Modifications:

  1. Replace the wet interior roof hatch.
  2. Replace the access tube roof hatch.
  3. Trim the platform hatch covers.
  4. Install ladder extension at the condensate platform.
  5. Install deflector bars on the fill/draw pipe.
  6. Install a chemical feed tap on the fill/draw pipe.
  7. Replace the expansion joint.
  8. Replace the mud valve.
  9. Replace the condensate drain line.
  10. Install an overflow flap gate.
  11. Install a fall prevention device on the basebell ladder.
  12. Install a pressure vacuum vent.
  13. Install a seal at the access tube air gap.
  14. Weld a rigging lug on the bowl.
  15. Install opening for ventilation in the basebell.
  16. Reroute the overflow pipe and install a duck bill check valve - alternate.
  17. Install a shutter for a ventilation system in the basebell.
  18. Install a flow meter on the fill/draw pipe.
  19. Replace the dry interior light bulbs.
  20. Install electrical receptacle for ventilation.
  21. Install an electrical receptacle for the flow meter.

Cathodic Protection: Install an impressed current cathodic protection system.

Splash Pad: Install a concrete splash pad at the overflow pipe discharge.